Categories
OEZ (https://www.oez.com/)

LFN-80-4-100A-G

Residual current circuit breaker

«
LFN-80-4-100A-G
Product description:
In 80 A, Ue AC 230/400 V, Idn 100 mA, 4-pole, Inc 10 kA, type A, design G
Order Code: OEZ:42473
EAN: 8590125424734
Unit of measure pcs
Send a question to the product

Electrical parameters

Rated current80 A
Rated residual current100 mA
Voltage typeAC
Rated operating voltageAC 230/400 V
Rated operating voltage AC230/400 V
Min. rated voltage AC100 V
Max. rated voltage AC250/440 V
Rated conditional short-circuit current10 kA
Rated making and breaking capacity800 A
Rated frequency50 Hz
Surge resistance3 kA
Electrical endurance10000 cycles
Release delayYES
SelectivityNO

Physical parameters

Degree of protectionIP20
Number of modules4
Number of poles4
TypeA-G
Mountingon DIN rail

Mechanical parameters

Mechanical endurance10000 cycles

Dimensions

Width (netto)71,6 mm
Height (netto)90 mm
Depth (netto)79,7 mm
Weight (netto)0,4 kg
Basic package1 ks
Collated package- pcs

Connection

Connection cross-section Cu (solid) min.0,75 mm2
Connection cross-section Cu (solid) max.35 mm2

Working conditions

Ambient temperature min.-25 °C
Ambient temperature max.45 °C
climatic resistance28 cycles

Customs data

Customs Tariff85362090
Country of originDE
ALN
ECCNEAR99

Database data

PCK3862