Categories
OEZ (https://www.oez.com/)

LFN-40-2-100AC

Residual current circuit breaker

«
LFN-40-2-100AC
Product description:
In 40 A, Ue AC 230 V, Idn 100 mA, 2-pole, Inc 10 kA, type AC
Order Code: OEZ:42413
EAN: 8590125424130
Unit of measure pcs
Send a question to the product

Electrical parameters

Rated current40 A
Rated residual current100 mA
Voltage typeAC
Rated operating voltageAC 230 V
Rated operating voltage AC230 V
Min. rated voltage AC100 V
Max. rated voltage AC250 V
Rated conditional short-circuit current10 kA
Rated making and breaking capacity500 A
Rated frequency50 Hz
Surge resistance0,25 kA
Electrical endurance10000 cycles
Release delayNO
SelectivityNO

Physical parameters

Degree of protectionIP20
Number of modules2
Number of poles2
TypeAC
Mountingon DIN rail

Mechanical parameters

Mechanical endurance10000 cycles

Dimensions

Width (netto)35,8 mm
Height (netto)90 mm
Depth (netto)79,7 mm
Weight (netto)0,197 kg
Basic package1 ks
Collated package- pcs

Connection

Connection cross-section Cu (solid) min.0,75 mm2
Connection cross-section Cu (solid) max.35 mm2

Working conditions

Ambient temperature min.-25 °C
Ambient temperature max.45 °C
climatic resistance28 cycles

Customs data

Customs Tariff85362010
Country of originDE
ALN
ECCNN

Database data

PCK3862